CalcPanel

Motor Cable Size Calculator

Enter motor FLA (prefer NEC Table FLC for code work), voltage, phase, one-way length, and VD limit to screen branch conductors against NEC 2023 430.22 (ampacity ≥ 125% FLA; adopted edition may differ). Default: 14 A · 480 V · 3φ · 100 ft · 3% VD · copper.

Quick calculator

Conductor ampacity checked against NEC 430.22 (125% FLA). Voltage drop checked against your limit. Results update instantly.

Advanced calculator

Set voltage-drop limit, conductor material and termination basis. Ampacity still uses 125% FLA (NEC 430.22).

Choose 75°C only when the equipment listing/marking and adopted code permit that termination basis.

About this calculator

See all protection calculators on the hub. This screens motor branch conductors: ampacity must be ≥ 125% of FLA (NEC 430.22), then checks voltage drop against your limit. Example: 14 A FLA, 480 V 3φ, 100 ft copper → 12 AWG at about 1.00% VD using the conservative 60°C termination basis. Verify terminal markings, installation corrections, adopted-code small-conductor rules and the actual motor branch requirements. Get FLA first with the Motor FLA Calculator, then size OCPD with the Breaker Size Calculator. For non-motor circuits use the general Cable Size Calculator.

Screening conductor size

Result explanation

Screening conductor: 12 AWG Copper (60°C basis)

Assumptions: NEC 2023 Table 310.16 and NEC 430.22 minimum ampacity = 125% FLA; 60°C is the conservative default termination basis. Verify equipment markings, small-conductor rules, installation corrections and voltage-drop policy before installation.

Continue Your Calculation

With conductor size selected, screen overcurrent protection and verify end-voltage drop on the run.

NEC 2023 Table 310.16 ampacity basis

The calculator includes 60°C and 75°C column screens. It defaults to 60°C; use 75°C only when the equipment listing/marking and adopted NEC rules permit that termination basis. Values assume no more than three current-carrying conductors and 30°C ambient before adjustment/correction. Motor conductor ampacity is screened at 125% of the applicable motor FLC under NEC 430.22; final design must also apply the adopted edition, terminal limits, conductor insulation, ambient/grouping corrections and applicable small-conductor/protection rules.

Motor cable sizing formula

Step 1 — NEC 430.22 ampacity screen: minimum conductor ampacity = FLC × 1.25 using the FLC basis required by the adopted code.

Step 2 — Resistive voltage-drop screen: three-phase Vd = √3 × L × I × R ÷ 1000; single-phase Vd = 2 × L × I × R ÷ 1000. L is one-way feet and R is Ω/1000 ft.

Step 3 — Select the first table row that clears both checks. For the default 14 A, 480 V, three-phase, 100 ft copper case, 125% FLC is 17.5 A. The conservative 60°C basis selects 12 AWG and the resistive drop is about 1.00%. This remains a screening result: equipment markings, adopted-code small-conductor/protection rules, installation corrections, conductor count and short-circuit withstand can require a different conductor.

Worked motor cable sizing examples

Default production case: 14 A × 1.25 = 17.5 A. At 480 V three-phase and 100 ft, the 60°C copper basis returns 12 AWG with about 1.00% resistive drop.

Single-phase comparison: 28 A × 1.25 = 35 A. At 230 V and 75 ft, the 60°C copper basis returns 8 AWG with about 1.42% resistive drop.

Aluminum comparison: 70 A × 1.25 = 87.5 A. At 460 V three-phase and 150 ft, the 60°C aluminum basis returns 1/0 AWG with about 0.79% resistive drop.

These examples reproduce the production screening tables. They do not choose OCPD, raceway, final terminal rating, derating, parallel-conductor arrangements or short-circuit withstand.

Frequently asked questions

Why use 125% of motor FLC?

NEC 430.22 generally bases a single motor branch-circuit conductor ampacity on 125% of the applicable motor full-load current. Use the FLC source and exceptions required by the locally adopted edition.

Can I use the 75°C column?

Only when the equipment listing/marking and adopted termination-temperature rules permit it. This tool defaults to the 60°C column and requires an explicit selection for 75°C.

Does this choose the breaker or overload setting?

No. Conductor ampacity, short-circuit/ground-fault protection and overload protection are separate checks with different NEC motor rules.

How should starting current be handled?

Use motor or driven-equipment manufacturer inrush/locked-rotor data and a source-impedance study for starting voltage drop. This steady-state resistive screen does not predict motor-starting performance.