Transformer Full Load Amps Calculator (Primary & Secondary FLA)
Enter nameplate kVA, phase, and both winding voltages for primary and secondary FLA together. Default: 100 kVA, 480→208 V, 3φ → ~120 A / ~278 A. Prefer this over generic kVA to amps for transformer nameplates.
Quick calculator
Use line-to-line voltage for three-phase. Results update instantly.
Advanced calculator
Scale winding currents by operating load. Nameplate FLA still shown at 100%.
100% = nameplate FLA. Enter the operating load from the project load study or measured demand; this calculator does not assume a typical loading range.
About this calculator
Transformer nameplate FLA for both windings in one screen. Generic one-side conversion: kVA to Amps. Capacity from load: Transformer Size. Small voltage correction (208→240): buck-boost sizing. Hub: power calculator · transformer.
Primary and secondary FLA
Result explanation
Primary FLA: 120.3 A @ 480 V · Secondary FLA: 277.6 A @ 208 V.
Assumptions: Screening only. Verify the nameplate, tap position, conductor conditions, OCPD rules, and available fault current before procurement.
Continue Your Calculation
After you know both winding FLA values, screen transformer %Z and equipment SCCR before preliminary protection review.
Common three-phase transformer FLA chart
Approximate secondary FLA. Open the calculator with matching primary/secondary defaults where useful.
| kVA | 208 V | 480 V | 600 V | Open |
|---|---|---|---|---|
| 75 | 208 A | 90 A | 72 A | 75 @ 480→208 |
| 100 | 278 A | 120 A | 96 A | 100 @ 480→208 |
| 150 | 416 A | 180 A | 144 A | 150 @ 480→208 |
| 500 | 1,388 A | 601 A | 481 A | 500 @ 480→208 |
Transformer full-load current formula
Three-phase: FLA = kVA × 1,000 ÷ (√3 × line-to-line V). Single-phase: FLA = kVA × 1,000 ÷ V. PF is not used because transformer nameplate capacity is already kVA.
Example: 100 kVA, 480 V, 3φ: 100,000 ÷ (1.732 × 480) = 120.3 A. At 208 V secondary: 277.6 A.
Workflow: load → transformer kVA → this FLA tool → %Z fault screen → breaker screening. Small utility correction (208→240): buck-boost chart.
Use the right tool
| Goal | Tool |
|---|---|
| Primary + secondary FLA from nameplate kVA | This page |
| Any single-side kVA ↔ amps (not transformer-specific) | kVA to Amps |
| 208→240 / buck-boost unit kVA | Buck-boost sizing |
| SCCR / available fault vs marked rating | SCCR Calculator |
Frequently asked questions
How do I calculate transformer full-load amps?
Use kVA and the voltage of the winding you are checking. For three-phase, divide kVA × 1,000 by √3 × line-to-line voltage.
How many amps is a 100 kVA transformer?
At 480 V three-phase it is about 120.3 A; at 208 V three-phase it is about 277.6 A. Voltage side matters.
Is primary current the same as secondary current?
No. The lower-voltage winding carries more current for the same kVA.
Does FLA choose the breaker size?
No. It is an input to preliminary protection review; code and manufacturer rules still apply.
Why not use the generic kVA to amps calculator?
Same SI formula, but this page owns both windings, transformer charts, and the nameplate workflow. Use kVA to amps for generic converters not tied to a transformer nameplate.
Related Tools
- Available Fault Current Calculator
- Circuit Breaker Size Calculator
- Transformer kVA Calculator (Instant Free Sizing & Chart)
- kVA to Amps Calculator (Instant, Free) — Also Amps to kVA
- Buck Boost Transformer Sizing Calculator (Instant, Free Chart)
- Transformer Turns Ratio Formula Calculator
- Factory Load Calculator
- Electricity Load Factor Calculator
Related Guides
- Transformer Sizing Guide — Complete guide to transformer capacity calculation, kVA sizing, and load matching
- Transformer Rating Calculation — How to calculate transformer kVA rating from load current, voltage, and power factor
- Three-Phase Transformer Sizing — Step-by-step 3-phase transformer sizing with diversity factors and safety margins
- Transformer Efficiency & Loss Calculation — Calculate copper losses, core losses, and efficiency at different load levels