Conduit Fill Calculator
Check mixed THHN conductors against NEC Chapter 9 fill limits and the smallest trade size that passes. Use it after cable size, breaker size, and voltage drop.
Fill inputs
About this calculator
Fill percent is total THHN area divided by the raceway internal area. Limits are 53%, 31%, and 40%. Continue on the protection calculators hub.
Result
Planning estimate. Confirm the raceway area and insulation before you order conduit.
Continue Your Calculation
If fill fails, go back to cable size and reduce the conductor count or upsize the raceway.
Chapter 9 fill limits and THHN count chart
| Conductors | Maximum fill |
|---|---|
| 1 | 53% |
| 2 | 31% |
| 3 or more | 40% |
Maximum count of one THHN size, using the same areas as the calculator. Two conductors use the 31% limit, so a size can hold fewer wires than the 40% rule alone suggests. RMC is slightly larger than EMT; use the calculator for RMC and for mixed sizes.
| EMT trade size | #14 | #12 | #10 | #8 | #6 | #4 |
|---|---|---|---|---|---|---|
| 1/2 in | 12 | 9 | 5 | 3 | 1 | 1 |
| 3/4 in | 21 | 16 | 10 | 5 | 4 | 2 |
| 1 in | 35 | 25 | 16 | 9 | 6 | 4 |
| 1-1/4 in | 61 | 44 | 28 | 16 | 11 | 7 |
| 1-1/2 in | 83 | 61 | 38 | 22 | 16 | 9 |
| 2 in | 138 | 100 | 63 | 36 | 26 | 16 |
| PVC Schedule 40 | #14 | #12 | #10 | #8 | #6 | #4 |
|---|---|---|---|---|---|---|
| 1/2 in | 11 | 8 | 5 | 3 | 1 | 1 |
| 3/4 in | 20 | 15 | 9 | 5 | 4 | 1 |
| 1 in | 34 | 25 | 15 | 9 | 6 | 4 |
| 1-1/4 in | 59 | 43 | 27 | 15 | 11 | 7 |
| 1-1/2 in | 81 | 59 | 37 | 21 | 15 | 9 |
| 2 in | 135 | 98 | 62 | 35 | 25 | 15 |
Formula
Fill % = (sum of conductor areas ÷ internal raceway area) × 100. Example: three 10 AWG THHN in 3/4 EMT is 3 × 0.0211 / 0.533 × 100 ≈ 11.9%, under the 40% limit. Two #4 THHN in the same 3/4 EMT is 2 × 0.0824 / 0.533 × 100 = 30.9%, under the 31% limit for two conductors.
Worked example
Three 10 AWG THHN in 3/4 in EMT: about 11.9% fill, Pass, and 3/4 in is a passing trade size.
Two #4 THHN in 3/4 in EMT: 30.9% fill, Pass. A third #4 THHN is 46.4% and fails the 40% limit, so the chart allows 2.
FAQ
What NEC fill limits does this use?
Chapter 9 Table 1: 53% for one conductor, 31% for two, and 40% for three or more.
Can I mix wire sizes?
Yes. Enter up to three THHN groups. Fill uses the sum of their areas, which covers a mix of wire sizes.
Does this check jam ratio?
No. Jam ratio and the 24-inch nipple 60% exception are marked Not checked.
How many #4 THHN wires fit in 3/4 EMT?
Two. On this page's areas, two #4 THHN use 30.9% of 3/4 in EMT, just under the 31% limit for two conductors. Three #4 THHN would be 46.4%, over the 40% limit.
How many wires fit in 1 inch EMT?
It depends on the THHN size. With this page's areas and the Chapter 9 limits, 1 in EMT holds 35 of #14, 25 of #12, 16 of #10, 9 of #8, 6 of #6, or 4 of #4 when every wire is the same size. Mixed sizes use the three groups above.
What conduit types and trade sizes does this cover?
EMT, PVC Schedule 40, and RMC, in trade sizes 1/2 through 4 inch. IMC is not on this screen. EMT is thin steel tubing, PVC Schedule 40 is plastic, and RMC is threaded rigid metal. The count chart shows 1/2 through 2 inch; larger sizes stay in the calculator.
Related Tools
- 3-Phase Cable Size Calculator
- Voltage Drop Formula & Calculator (1φ/3φ/DC, Instant)
- Circuit Breaker Size Calculator
- Ground Wire Size Calculator
- Motor FLA Calculator (Full Load Amps by HP, kW & Voltage)
- Motor Cable Size Calculator (NEC 430.22 & Voltage Drop)
- VFD Sizing Calculator (Motor HP, Application & Derating)
- EV Charger Load Calculator (Instant Breaker & Amps)